The bypass factor, in case of sensible cooling of air, is given by (where td1 = Dry bulb temperature of air entering the cooling coil, td2 = Dry bulb temperature of air leaving the cooling coil and td3 = Dry bulb temperature of the cooling coil)
A. $$\frac{{{\text{t}}{{\text{d}}_1} - {\text{t}}{{\text{d}}_3}}}{{{\text{t}}{{\text{d}}_2} - {\text{t}}{{\text{d}}_3}}}$$
B. $$\frac{{{\text{t}}{{\text{d}}_2} - {\text{t}}{{\text{d}}_3}}}{{{\text{t}}{{\text{d}}_1} - {\text{t}}{{\text{d}}_3}}}$$
C. $$\frac{{{\text{t}}{{\text{d}}_3} - {\text{t}}{{\text{d}}_1}}}{{{\text{t}}{{\text{d}}_2} - {\text{t}}{{\text{d}}_3}}}$$
D. $$\frac{{{\text{t}}{{\text{d}}_3} - {\text{t}}{{\text{d}}_2}}}{{{\text{t}}{{\text{d}}_1} - {\text{t}}{{\text{d}}_3}}}$$
Answer: Option B
Solution (By Examveda Team)
The bypass factor, in case of sensible cooling of air, is given by $$\frac{{{\text{t}}{{\text{d}}_2} - {\text{t}}{{\text{d}}_3}}}{{{\text{t}}{{\text{d}}_1} - {\text{t}}{{\text{d}}_3}}}$$Where,
td1 = Dry bulb temperature of air entering the cooling coil,
td2 = Dry bulb temperature of air leaving the cooling coil,
td3 = Dry bulb temperature of the cooling coil